Wire Gauge
Cu stranded tin-plated wire
| Rated Amps
| mV drop in 10ft Wire at ...
| Crimp Terminal
|
AWG
| mOhms/ft
| Ckt Breaker
| Fuse
| 1A
| 3A
| 5A
| 7A
| 10A
| 15A
| 20A
| 30A
| 60A
|
24 |
28.40 |
1 |
1 |
284 |
|
|
|
|
|
|
|
|
Red |
22 |
16.20
| 5
| 5 |
162
| 486
| 810
| |
|
|
|
|
|
20 |
9.88 |
7.5 |
5 |
98.8 |
296 |
494 |
692 |
|
|
|
|
|
18 |
6.23 |
10 |
10 |
62.3 |
187 |
312 |
436 |
623 |
|
|
|
|
16 |
4.81
| 15
| 10 |
48.1
| 144
| 241
| 337
| 481
| 722
| |
|
|
Blue |
14 |
3.06 |
20 |
15 |
30.6 |
91.8 |
153 |
214 |
306 |
459 |
612 |
|
|
12 |
2.02 |
30 |
20 |
20.2 |
60.6 |
101 |
141 |
202 |
303 |
404 |
606 |
|
Yellow |
10 |
1.26
| 40
| 30 |
12.6
| 37.8
| 63
| 88.2
| 126
| 189
| 252
| 378
| |
8 |
.70 |
50 |
50 |
7.0 |
21 |
35 |
49 |
70 |
105 |
140 |
210 |
|
|
6 |
.44
| 80
| 70 |
4.4
| 13.2
| 22
| 30.8
| 44
| 66
| 88
| 122
| 264
|
4 |
.28 |
100 |
70 |
2.8 |
8.4 |
14 |
19.6 |
28 |
42 |
56 |
84 |
168 |
2 |
.18 |
125 |
100 |
1.80 |
9.40 |
9.0 |
12.6 |
18 |
27 |
36 |
54 |
108 |
Circuit Breakers
Breaker Rating Amps
| Tyco Breaker W58 (PushReset)
| Tyco Breaker W31 (ToggleSwitch)
| Mech Products Series-16
|
R +/-30% mOhms
| V-drop at Rated-I
| R max mOhms
| V-drop at Rated-I
| R typ mOhms
| V-drop at Rated-I
|
1 |
1350 |
1.35 V |
610 |
.610 V |
|
|
5
| 26
| .130 V
| 30
| .150 V
|
|
|
7.5 |
20 |
.150 V |
20 |
.150 V |
|
|
10
| 14
| .140 V
| 10
| .100 V
|
|
|
15
| 10
| .150 V
| 6.0
| .090 V
|
|
|
20
| 5.0
| .100 V
| 4.0
| .080 V
|
|
|
30 |
4.0 |
.120 V |
3.0 |
.090 V |
|
|
40 |
|
|
2.0 |
.080 V |
|
|
50 |
|
|
2.0 |
.100 V |
|
|
60
|
|
|
|
| 1.00
| .060
|
70 |
|
|
|
|
.86 |
.060 |
Mil Std: MIL-W-22759/16-XX or MIL-W-81044/../XX (where: XX = AWG)
(Mfr: Raychem SPEC 44), from AC 43.13-1B, Part 11
Home